Type DSH TT 2P 255 Part No. 941 110 SPD according to EN 61643-11 / IEC 61643-1/-11 Type 1 / Class I Energy coordination with terminal equipment Type 1 + Type 2 Energy coordination with terminal equipment (≤ 5 m) Type 1 + Type 2 + Type 3 Nominal a.c. voltage (UN) 230 V Max. continuous operating a.c. voltage (UC) 255 V Lightning impulse current (10/350 μs) [L+N-PE] (Itotal) 25 kA Specific energy [L+N-PE] (W/R) 156.25 kJ/ohms Lightning impulse current (10/350 μs) [L-N]/[N-PE] (Iimp) 12.5 / 25 kA Specific energy [L-N]/[N-PE] (W/R) 39.06 / 156.25 kJ/ohms Nominal discharge current (8/20 μs) [L-N]/[N-PE] (In) 12.5 / 25 kA Voltage protection level [L-N]/[N-PE] (UP) ≤ 1.5 / ≤ 1.5 kV Follow current extinguishing capability [L-N]/[N-PE] (Ifi) 25 kArms/ 100 Arms Follow current limitation/Selectivity no tripping of a 32 A gL/gG fuse up to 25 kArms(prosp.) Response time (tA) ≤ 100 ns Max. mains-side overcurrent protection 160 A gL/gG Temporary overvoltage (TOV) [L-N] (UT) 440 V / 5 sec. Temporary overvoltage (TOV) [N-PE] (UT) 1200 V / 200 ms TOV characteristic withstand Operating temperature range (TU) -40 °C...+80 °C Operating state/fault indication green / red Number of ports 1 Cross-sectional area (L, N, PE,9) (min.) 1.5 mm2solid/flexible Cross-sectional area (L, N, PE,9) (max.) 35 mm2stranded/25 mm2flexible For mounting on 35 mm DIN rails acc. to EN 60715 Enclosure material thermoplastic, red, UL 94 V-0 Place of installation indoor installation Degree of protection IP 20 Capacity 2 module(s), DIN 43880 Approvals KEMA, UL Weight 275 g GTIN 4.01336E+12 PU 1 pc(s) Part No. 941 110